Parameter
| Nec. | MAIN ARTI DATA | Unitas |
| |
| 1 | Rated Voltage | kV | 12 | |
| 2 | Fulmen impetus sustinere intentione (Peak) | kV | 75 | |
| 3 | Brevi tempore (1min) Power-frequency resistere intentione | kV | 42 | |
| 4 | Rated Frequency | Hz | 50/60 | |
| 5 | Ratum Current | A | 630 | |
| 6 | Rated breve tempus sustine Current | kA | 6.3 | |
| 7 | Rated spatium breve spatium | s | 4 | |
| 8 | Rated Breaking Current | A |
| |
| 9 | Limiting Breaking Current | kA |
| |
| 10 | Rated Condita Current | kA | 6.3 | |
| 11 | Rated Operating Frequency | AC-3 | Res / h * |
|
| AC-4 | 300 | |||
| 12 | Brevi tempore Operating Frequency | Res / h * |
| |
| 13 | Utendo Categoria | AC |
| |
| 14 | Patientia electrica | AC-3 | Operationes | 2.5*105 |
| AC-4 | 5*104 | |||
| 15 | Mechanica patientia | Operationes | 3.0*105 | |
| 16 | Clearance inter Open Contactus | N | 5.5~7 | |
| 17 | Contactus claudunt Ob folles et atmosphaerae | N | 80+ -10 | |
| 18 | Contra vim Contactum in plena Stroke | μΩ | 110+ -10 | |
| 19 | Ambitus Resistentia ad Min.Ratum Contact Force | mm | <=160 | |
| 20 | Contact Low Erosion |
| 1.5 | |
| 21 | Missa de Movendis Partibus |
| 0.49 | |
| 22 | Internum Gas Pressura | Pa | <=1.33*10-3 | |
| 23 | Fasciae vita | Annus | 20 | |
Forma ratio drawing